NFPA 2001 Clean Agent Enclosure Design Webinar

Why Testing is Critical

  • Clean agents are discharged at high pressure (~5–25 psf or several hundred Pa), and the room must contain that pressure without structural damage.
    ([turn0search2], [turn0search1])

  • Leakage also affects how long the agent remains at effective concentration—known as the hold time.
    ([turn0search2], [turn0search1])

Door-Fan Measurements & Annex C Models

A door-fan test measures leakage area by pressurizing and depressurizing the space; results feed into Annex C formulasin NFPAĀ 2001 to predict how long the agent will remain at protective levels and what peak pressures will be reached.
([turn0search2], [turn0search1])

Dual Leakage Area Measurements

NFPAĀ 2001 now requires two distinct leakage measurements:

  1. Hold-Time Leakage – to determine how well the room retains agent over time.

  2. Peak-Pressure Leakage – used to ensure pressure during discharge doesn’t exceed structural limits—per a ā€œspecified enclosure pressure limit.ā€

    • If hold-time sealing could create dangerously high peak pressure, a pressure relief vent (PRV) may be required.
      ([turn0search1], [turn0search2])

Best Practices in Design & Testing

  • Solid seals at ceilings and continuous wall connections above ceiling tiles.

  • False ceilings require both upper and lower leakage tests—using separate fan ports.

  • Installing a PRV ventilates excessive pressure if hold-time sealing inadvertently raises peak pressure past the safe threshold.
    ([turn0search2], [turn0search1])

Final Takeaway

This webinar and NFPA-compliant testing ensure system designers and installers can:

  • Calculate and verify both hold time and peak pressure using door-fan data and Annex C.

  • Ensure occupant safety by avoiding structural over-pressurization.

  • Maintain compliance by performing the dual-measurement enclosure integrity test as required