Assemble the aluminum frame by snapping together numbered pieces.
Mount the calibrated blower fan and insert the correct range plate to match testing conditions. For residences, begin with the mid plate and adjust as needed.
Connect the yellow static tube from the house to the fan and the red pressure reference tube to the gauge.
Ensure tubing is routed freelyāno kinks or sharp bendsāto avoid false readings.
Access Settings ā Baseline to zero the gauge using room air.
On the home screen, select your setup (blower door frame + mid plate) to configure the gauge for testing
Create negative pressure (commonly 50āÆPa), then stabilize.
Check for spikes or anomalies from wind, HVAC activity, or tube disturbances.
Read CFM50 directly from the gauge once readings stabilize.
The system is self-containedāno software neededāand enables a quick, reliable, compliant test.
The DMā32 simplifies process with Set Pressure, @Pressure, and auto-zero features.
Frame and gauge configurations are intuitive and repeatable, matching built-in testing protocols