Your digital gauge (e.g., DMā32 or DMā2) must be configured to match:
The connected equipment (e.g., blower door fan or DucTester model)
The installed flow restriction (range ring or plate) on the fan
If these don’t align, the gauge won’t calculate airflow correctly. Data may be offāor unusable entirely.
On the gauge’s Home screen, tap āRange/Deviceā
If your device isnāt listed, tap āChange Deviceā to select the correct one
Choose the exact model you’re using (e.g. āDU200 DucTesterā, āModelāÆ3350SR blowerā).
This aligns the gauge’s calculations with the fanās performance characteristics.
Select the installed restriction (e.g. small/medium/open).
The gauge uses this to determine the airflow curve correctly.
When you return to the Home screen, top-bar icons will show:
Device name
Range setting
Result mode ready (e.g., CFH@50Pa on Channel B)
Always check after power-cycle: Gauges remember the last-used settings, which may not match your current test setup
Double-check before testing: A mismatchālike selecting an āopenā range when a restricted ring is installedācan result in wildly incorrect readings
Correct mistakes early: If you notice odd or off-scale values, revisit the Device/Range menu before capturing data